CRAH and CRAC Units spec kit
CRAH units move the cold air through the data hall. CRAC units make their own cold with a compressor. Which one you pick shapes your plant, your piping and your efficiency for the life of the room.
Where it fits in a critical building
What to put in the spec
Starter spec language
Furnish chilled water computer room air handlers rated per AHRI 1360 at the design conditions.
Units shall use EC fans with N+1 fan redundancy inside each unit.
Provide factory mounted two way control valves with the actuator listed on the schedule.
Supply and return sensors shall be factory installed and wired to the unit controller.
Provide a unit to unit network with the building management system on BACnet.
Starter language only. Edit it for your project and check it against the current standards and your own master spec.
Standards to reference
- AHRI 1360 computer room air conditioners
- ASHRAE TC 9.9 thermal guidelines for data centers
- UL 1995 listing
- ASHRAE 90.4 energy standard
- NFPA 75 information technology equipment
Questions to ask the manufacturer
- What is the real capacity at our return air temperature, not the catalog point?
- How many fans can fail before capacity drops?
- How long does a filter or fan swap take with the unit running?
- What happens to airflow if the controls network drops?
- What are the lead times for the fan and valve assemblies?
Companies commonly specified
Examples only, in no order. This is not an endorsement or a complete list. Always check current ratings and availability with the manufacturer.