To specify chillers well, an engineer has to balance reliability, efficiency, water use and space. Chillers are the largest single mechanical purchase in most data centers and hospitals, and the spec controls cost for the life of the building. This guide covers the main choices and the items that belong in the written section.

Air cooled or water cooled
Air cooled chillers reject heat directly to outdoor air. They use no cooling tower water, are simpler to maintain, and suit sites where water is scarce or costly. Water cooled chillers reject heat to a condenser water loop and a cooling tower. They are usually more efficient at full size and are common in large campuses and hospitals, but they add towers, pumps, water treatment and water consumption.
Water use is now a design driver for data centers. Our posts on water use effectiveness and reclaimed water explain how owners weigh these tradeoffs.
Compressor types
Centrifugal chillers dominate large plants, especially with magnetic bearing, oil free compressors that run well at part load. Screw chillers cover mid size loads and are common in air cooled packages. Scroll chillers serve smaller loads. Match the compressor type to the load profile, since most plants run at part load most of the year.
Efficiency and part load performance
Specify efficiency at both full load and part load. Integrated part load value, or IPLV, and non standard part load value, or NPLV, reflect how chillers actually run. Ask for performance certified under AHRI Standard 550/590 and require test data in the submittal. Variable speed drives, higher chilled water temperatures and free cooling economizers all reduce energy use and improve power usage effectiveness.
Refrigerants
Refrigerant choice is now a regulatory and eco issue. Many older high global warming potential refrigerants are being phased down under the AIM Act in the United States. Ask the manufacturer for current options, global warming potential, flammability class and any safety code requirements for the machine room. Include leak detection and refrigerant monitoring where codes require them.
Redundancy and controls
Define the redundancy level in the spec, for example N plus one or 2N, and state how many chillers must run at design conditions. Require communication with the building automation system over open protocols such as BACnet, and require staging logic that handles failure without a trip. For liquid cooled racks, chilled water temperature setpoints may be higher, which opens more free cooling hours.
What goes in the section
List acceptable manufacturers and a basis of design. State capacity, entering and leaving water temperatures, flow, allowable pressure drop, electrical characteristics, sound limits, and efficiency targets. Require factory witnessed testing for critical plants, startup by the manufacturer, a warranty period, and training. Coordinate isolation valves, strainers, flow meters and vibration isolation with the piping sections.
Sizing, redundancy and sound
Size chillers from a real load calculation, not a rule of thumb. For data centers, include the planned growth by phase and state which chillers are installed on day one and which are future pads. For hospitals, include seasonal swings, since operating rooms and patient floors need cooling and dehumidification all year. Decide whether the plant must keep running through a single failure, a maintenance event, or both, and write that down. Sound limits matter too. A plant next to a patient tower or a residential neighbor needs acoustic criteria, barriers or low sound fan packages, and the spec should state the allowable level at a defined distance.
Piping accessories that belong with the chiller
A chiller is only as reliable as the piping around it. Specify isolation valves on the evaporator and condenser, strainers upstream to protect tubes, flow switches, pressure and temperature test ports, and vibration isolators on connections. Add flow meters and energy meters if the owner wants to track performance. Coordinate bypass piping for plants that use free cooling, and specify check valves where pumps could backflow through an idle machine. Many commissioning delays start with a missing accessory, so list each one in the section instead of leaving it for the drawings.
Eco friendly options worth writing in
Several choices lower energy and environmental impact without hurting reliability. Variable speed oil free centrifugal machines cut part load energy. Heat recovery chillers send rejected heat to reheat coils, domestic hot water or a nearby district system. Low global warming potential refrigerants reduce lifetime climate impact. Higher chilled water setpoints increase free cooling hours. Owners that chase carbon goals also ask for environmental product declarations and take back programs. Each of these should be a requirement or an alternate in the spec, with a clear way to compare bids.
Frequently asked questions
What is IPLV?
Integrated part load value is a single efficiency number that weights performance at several load points, reflecting typical operation better than full load efficiency alone.
Are air cooled chillers better for water use?
They use no tower water, so they save water, though they can use more electricity in hot climates. The right answer depends on climate and local water costs.
Why do hospitals use water cooled plants?
Large hospitals run continuous cooling and benefit from the high efficiency of central plants, along with N plus one or better redundancy.